Difference between revisions of "DCOM Volume I Appendix I"

From Ministry of Water DCOM Manual
 
Line 13: Line 13:
 
with them are as follows:
 
with them are as follows:
  
[[Image:AppendixITable1.PNG|999px|link=DCOM_Volume_I]] <br>
+
[[Image:AppendixITable1.PNG|780px|link=DCOM_Volume_I]] <br>
  
 
If hardness is too high it results into precipitation of soap, scaling on pipes,
 
If hardness is too high it results into precipitation of soap, scaling on pipes,
Line 24: Line 24:
 
2007). The scale of hardness is shown in Table I.2:
 
2007). The scale of hardness is shown in Table I.2:
  
[[Image:AppendixITable2.PNG|999px|link=DCOM_Volume_I]] <br>
+
[[Image:AppendixITable2.PNG|780px|link=DCOM_Volume_I]] <br>
  
 
'''Temporary and Permanent Hardness'''<br>
 
'''Temporary and Permanent Hardness'''<br>
Line 34: Line 34:
 
at high temperatures.
 
at high temperatures.
  
[[Image:AppendixItable3.PNG|999px|link=DCOM_Volume_I]] <br>
+
[[Image:AppendixItable3.PNG|780px|link=DCOM_Volume_I]] <br>
  
  
 
Previous Page: [[DCOM_Volume_I_Appendix_H|DCOM_Volume_I_Appendix_H]] <<  >> Next Page: [[DCOM_Volume_I_Appendix_J|DCOM_Volume_I_Appendix_J]]
 
Previous Page: [[DCOM_Volume_I_Appendix_H|DCOM_Volume_I_Appendix_H]] <<  >> Next Page: [[DCOM_Volume_I_Appendix_J|DCOM_Volume_I_Appendix_J]]

Latest revision as of 16:26, 2 June 2021

APPENDIX I: MEASUREMENTS OF WATER HARDNESS

Hardness and its Measurement
Hardness is expressed in terms of mg/l by weight and in terms of calcium carbonate. Water with hardness not exceeding 70 mg/l is termed ‘soft’ and above that 'hard'. In public water supplies, it used to be customary to reduce carbonate hardness to 35 - 40 mg/l and total hardness to between 50 and 100 mg/l. However as indicated above this is no longer recommended unless hardness exceeds about 130 mg/l, but should still be practised for strictly industrial supplies of water.

Hardness = Σ divalent cations = Ca2+ + Mg2+ + Fe2+ + Mn2+ + Sr2+..
The principle cations causing hardness in water and major anions associated with them are as follows:

AppendixITable1.PNG

If hardness is too high it results into precipitation of soap, scaling on pipes, boilers, cooling towers, heat exchangers. If hardness is too low, the water becomes corrosive. Hard water interferes with almost every cleaning task from laundering and dishwashing to bathing and personal grooming (IANR, Water Quality 1996). Hard water ranges between 120-250 mg/L as CaCO3 or beyond 250 mg/L as CaCO3 for very hard waters. The acceptable water hardness range is between 60-120 mg/L as CaCO3 (Dipa Dey, Amanda Herzog and Vidya Srinivasan, 2007). The scale of hardness is shown in Table I.2:

AppendixITable2.PNG

Temporary and Permanent Hardness
Hardness can be described as temporary or permanent as shown in the Table: I.3 Carbonate hardness is called temporary because it precipitates readily at high temperatures since it is sensitive to heat and precipitates readily at high temperatures. Therefore, hardness can be removed by boiling the water. Noncarbonate hardness is called permanent because it does not precipitate readily at high temperatures.

AppendixItable3.PNG


Previous Page: DCOM_Volume_I_Appendix_H << >> Next Page: DCOM_Volume_I_Appendix_J